AIRBOOST FAN ASSISTED FLOOR TILES  
Adjustable controls allow multiple settings of air-flow depending on the amount needed at any certain time.

The Airboost fan assisted system offers direct cooling to those hard to cool areas where clusters of high-density servers have created hotspots. Adjustable controls allow multiple settings of air-flow depending on the amount needed at any certain time. The adjustment of fan speed is made from the top of the tile to allow quick and easy fan control. Closed loop (Temperature controlled) speed control available as an option.

No downtime or movement of racks is required for the installation of an Air-Boost unit and one Air-Boost can provide cooling for two or three adjacent racks. If larger areas require cooling, multiple Air-Boost units can be used at the same time.
 
Airboost can be considered a “greening” solution as well. Many times data centers are kept cooler than necessary just to cool a few high density areas. This over-cooling is used to keep the hotspots under control but with a Airboost solution in place, the overall room temperature can be increased as the Airboost will control the individual and problematic hotspots without requiring an over-cooled data center.  
 

TYPICAL INSTALLATION

FAN SPECIFICATIONS
       
Wall ring Die Cast Aluminium Type of Protection IP 44
Blades Steel Sheet, coated in Black Insulation Class B
Number of Blades 7 Bearings Maintenance –Free Ball Bearing
RPM 2550 Motor Protection TOP wired internally
Approvals VDE, UL, CSA, CCC, GOST Protection Class I
    Product Confirming to Standards EN 60335-1, CE

Air Flow Evaluation Case-I Air Flow Evaluation Case-II
Under Floor Static Pressure .029 inches/H2O Under Floor Static Pressure .013 inches/H2O
Airflow with Air Boost Airflow with Air Boost
High: 1508 CFM High: 1696 CFM
Medium: 1350 CFM Medium: 1410 CFM
Low: 960 CFM Low: 725 CFM
Off: 539 CFM Off: 240 CFM
Product Confirming to Standards EN 60335-1, CE
Server Cabinet inlet temperature at the top of the rack
Before AirBoost: 26.8 °C
After AirBoost: 22.7 °C
 
 
 